Top ventilation for top chefs

Condensation hoods

Jeven’s condensation hoods are the most effective hoods on the market for removing condensate water.

The Jeven condensation hoods has a unique water and vapor separation baffle structure, condensate separators and edge grip on both long sides.

Condensation hoods are intended for kitchens, where a large amount of water vapor is released from kitchen equipment, such as dishwashers. Thanks to the modular design of the hoods, they can be manufactured without partitions.

PRODUCT STRUCTURE

  1. Measurement tap for the supply air (behind the condensation baffles)
  2. LED lights
  3. Condensation baffles, measurement tap for exhaust air
  4. Supply air connection and damper unit
  5. Exhaust air connection and damper plates
  6. Supply air unit (detachable)

Light

By default, every hood module comes with an energy efficient LED light fixture integrated to the hood’s roof.

The light fixture has a cable which should be connected to a junction box with a cable lock. The connection cable is equipped with a quick connector and it must be positioned in such way that it is not exposed to mechanical or thermal stress.

IP 66 integrated LED lamp
4000 K, CRI>84
incl. 2 m HF-connection cable (Halogen Free, type 3×1,5 mm²)

FUNCTIONING PRINCIPLE

JSKI

  1. Dirty air rises due to temperature differences against the ceiling of the hood.
  2. Condensated water and grease are effectively removed by the baffles.
  3. Clean air is extracted.
  4. Supply air is introduced through supply air columns
  5. The supply air blowing pattern and blowing direction can be varied.

JKI

TECHNICAL INFORMATION - EXHAUST AIR

The recommended exhaust flow rate is max. 250 l/s per 315 mm spigot, duct velocity 3.2 m/s. The hoods are equipped with a suitable type of condensation baffles (pressure level 30-50 Pa).
The recommended exhaust flow is 100 to 200 l/s per hood meter. The hoods are equipped with a suitable type of condensation baffles.

Recommended exhaust flow/spigot

Spigot size ØExhaust flow
mml/sm³/h
200-120-430
250120-200430-720
315200-300720-1080
400300-5001080-1800

Pressure loss and sound data

Condensation baffle type 1/1

Sound power level, Lw
Sound power level Lw in each octave band is computed by adding the corresponding factor, Kok to the sound power level LpA: Lw=LpA + Kok.

Factor, Kok

Hz125250500100020004000
Kok654-2-8-15
tol.±3±3±2±2±3±4

Condensation baffle type 2/1

Sound power level, Lw
Sound power level Lw in each octave band is computed by adding the corresponding factor, Kok to the sound power level LpA: Lw=LpA + Kok.

Factor, Kok

Hz125250500100020004000
Kok654-2-8-15
tol.±3±3±2±2±3±4

Effect of damper plate on sound level

In practice, the sound level will not increase if the pressure difference increases by 20 pascals or less. When the differential pressure rises, the sound level of about 45 pascals increases by about 5 decibels. Precise sound additions can be found in the design software (MagiCAD, CADS Planner Hepac).

TECHNICAL INFORMATION - SUPPLY AIR

The canopies are supplied from the factory with suitable air flow rates for a pressure level of 25-35 Pa.

Supply air unitø160ø200ø250
Width, mm200500500
Height, mm500290500
Air flow40-70 l/s60-90 l/s100-150 l/s
K1 (m³/h)77,096,0192
K2 (l/s)21,426,753,3
 Q=Kx√Pm       Pm=(Q/K)²Pa    

Pressure loss, sound data and throw length/supply air unit

Spigot ø200 mm.
Unit width 500 mm. Hood height 330 mm. Measurement after 90° curve.

Hz125250500100020004000
Kok-274-5-19-26
tol.±6±4±2±2±3±5

Spigot ø160 mm.
Unit width 200 mm. Hood height 540 mm. Measurement after 90° curve.

Hz125250500100020004000
Kok-2121-7-16
tol.±3±3±2±2±3±4

Spigot ø250 mm.
Unit width 500 mm. Hood height 540 mm. Measurement after 90° curve.

Hz125250500100020004000
Kok684-5-10-18
tol.±3±3±2±2±3±4

The sound power level (Lw) in each octave band is computed by adding the corresponding factor Kok to the sound pressure level (LpA), as in Lw= LpA+Kok


Supply air blow alignment

Jeven supply air columns deliver a controlled and flexible distribution of the supply air. It is possible to wash the supply air columns in a dishwasher and the inside of the supply air chambers is easy to clean. These columns allow an individual adjustment of air patterns and air flows, which means a better indoor climate for the kitchen staff.

Horizontal alignment of the supply air
The supply air blow direction can be aligned left or right by moving the air control plates inside the supply air units. The control plates are marked in red in the pictures.

Vertical alignment of the supply air
The supply air blow direction can be aligned up or down by turning the horizontal air control plates inside the supply air units. The control plates are marked in red in the pictures.

Air blow directions alignment nearby supply air column
Supply air blowing direction can be aligned by turning the rotatable blowing nozzles at the bottom of the supply air column. The rotatable nozzles are marked in red in the pictures.


Sound attenuation, dB

Hood heightSpigot125 Hz250 Hz500 Hz1000 Hz2000 Hz4000 Hz
330 mmø200171010111824
540 mmø1602485121724
540 mmø2501697111623

Product info

  • Condensation Hoods

    Product Brochure

Product code

JSKI – 3000x1500x540 – 2×250 – 2×315280 l/s – 450 l/s – CB

  • The canopy’s base material is stainless steel, AISI 304
  • Covering boards available to enclose the area between the top of the hood and the ceiling.