Product structure

- UV-Turbo grease filter
- Exhaust air connection and damper plates
- LED lights
- Supply air unit with removable front panel
- Supply air connection and damper unit

Light
By default, every hood module comes with an energy efficient LED light fixture integrated to the hood’s roof.
The light fixture has a cable which should be connected to a junction box with a cable lock. The connection cable must be positioned in such way that it is not exposed to mechanical or thermal stress.
IP 66 integrated LED lamp
4000 K, CRI>84
inc 2 m HF-connection cable (Halogen Free, type 3×1,5 mm²)
Technical information - Exhaust air
TurboSwing® and UV light combined filtering efficiency

UV-Turbo, spigot ø315
Air flow l/s | K1 (l/s) | Air flow m³/h | K2 (m³/h) | Pressure loss |
100 - 200 | 60,5 | 360 - 720 | 218 | 20 - 60 Pa |
Q=Kx√Pm Pm=(Q/K)²Pa | |
Pressure loss and sound data
TurboSwing 750 rpm
Sound pressure level 10 dB(A) with room suppression

TurboSwing 1100 rpm
Sound pressure level 10 dB(A) with room suppression

Sound power level, Lw
Sound power level Lw in each octave band is computed by adding the corresponding factor, Kok to the sound power level LpA: Lw=LpA + Kok.
Hz | 125 | 250 | 500 | 1000 | 2000 | 4000 |
Kok | 7 | -1 | -5 | -5 | -7 | -6 |
tol. | ±3 | ±3 | ±2 | ±2 | ±3 | ±4 |
Adjustment and measurement

K-factor
Supply air unit | ø160 | ø200 | ø250 |
Width mm | 200 | 500 | 500 |
Height mm | 500 | 290 | 500 |
Air flow | 40-70 l/s | 60-90 l/s | 100-150 l/s |
K1 (m³/h) | 77,0 | 96,0 | 192 |
K2 (l/s) | 21,4 | 26,7 | 53,3 |
Q=Kx√Pm Pm=(Q/K)²Pa |
Technical information - supply air
Supply air unit | ø160 | ø200 | ø250 |
Width mm | 200 | 500 | 500 |
Height mm | 500 | 290 | 500 |
Air flow | 40-70 l/s | 60-90 l/s | 100-150 l/s |
K1 (m³/h) | 77,0 | 96,0 | 192 |
K2 (l/s) | 21,4 | 26,7 | 53,3 |
Q=Kx√Pm Pm=(Q/K)²Pa |
The canopies are supplied with suitable air flow rates for a pressure level of 25-35 Pa.
Pressure loss, sound data and throw length/supply air unit
Spigot ø250mm, 100-150 l/s. Hoods height 540 mm. Measurement after 90° curve.

Hz | 125 | 250 | 500 | 1000 | 2000 | 4000 |
Kok | 6 | 8 | 4 | -5 | -10 | -18 |
tol. | ±3 | ±3 | ±2 | ±2 | ±3 | ±4 |
Spigot ø200, 60-90 l/s. Hoods height 330 mm. Measurement after 90° curve.

Hz | 125 | 250 | 500 | 1000 | 2000 | 4000 |
Kok | -2 | 7 | 4 | -5 | -19 | -26 |
tol. | ±6 | ±4 | ±2 | ±2 | ±3 | ±5 |
Spigot ø160 mm, 40-70 l/s. Hoods height 540 mm. Measurement after 90° curve.

Hz | 125 | 250 | 500 | 1000 | 2000 | 4000 |
Kok | -2 | 1 | 2 | 1 | -7 | -16 |
tol. | ±3 | ±3 | ±2 | ±2 | ±3 | ±4 |
The sound power level (Lw) in each octave band is computed by adding the corresponding factor Kok to the sound pressure level (LpA), Lw= LpA+Kok
Sound attenuation (dB), damper open.
Hoods height | Spigot | 125 Hz | 250 Hz | 500 Hz | 1000 Hz | 2000 Hz | 4000 Hz |
330 mm | ø200 | 17 | 10 | 10 | 11 | 18 | 24 |
540 mm | ø160 | 24 | 8 | 5 | 12 | 17 | 24 |
540 mm | ø250 | 16 | 9 | 7 | 11 | 16 | 23 |
Supply air blow alignment
Jeven supply air columns deliver a controlled and flexible distribution of the supply air. It is possible to wash the supply air columns in a dishwasher and the inside of the supply air chambers is easy to clean. These columns allow an individual adjustment of air patterns and air flows, which means a better indoor climate for the kitchen staff.
Horizontal alignment of the supply air
The supply air blow direction can be aligned left or right by moving the air control plates inside the supply air units. The air control plates are marked in red in the pictures.

Vertical alignment of the supply air
The supply air blow direction can be aligned up or down by turning the horizontal air control plates inside the supply air units. The air control plates are marked in red in the pictures.

Air blow directions alignment nearby supply air column
Supply air blowing direction can be aligned by turning the rotatable blowing nozzles at the bottom of the supply air column. The rotatable nozzles are marked in red in the pictures.

Adjustment and measurement

Accessories
UV-SwingControl monitoring unit

UV-SwingControl has been developed to indicate potential problems in the operation of the UV-TurboSwing equipment. UV-SwingControl produces an immediate alert upon failure. UV-TurboSwing equipment failures can be identified locally or the building automation system may be notified.
UV-SwingControl monitors UV-Turbo motors rotation speed and UV-lights function. Rotation speed can be selected between 750 and 1100 rpm. The unit gives an alarm if the UV-Turbo’s motor rotation speed falls below 200 rpm or the UV-light has an error in function.
The status information of the locally connected UV-Turbo equipment is displayed on the LED screen of UV-SwingControl monitoring unit. Read more about UV-SwingControl

Ansul-Fire Suppression System is available to all Jevenin hoods.
Read more

Jeven Flow application
Jeven flow application can be connected with your UV-SwingControl monitoring unit to see the status information of UV-Turbo units. Read more about JevenFlow.
Covering boards
Covering boards to enclose the area between the top of the hood and the ceiling.

Product code
JSI – R – UV-TURBO – 3000x1500x540 – 4×250 – 3×315 + 480 l/s – 550 l/s – CB – UV-SC – FP
- UV-Turbo hoods are equipped with TurboSwing filters, ozone free UV light and integrated LED lights.
- The canopy’s base material is stainless steel, AISI 304
Connections
Electrical installation

- Connector cord
- Junction box
- Led light
- Limit switch
The HPAC designer designates the types and locations of wired products in the plans.
The electrical designer designates to the plans, the location of the safety switch (compulsory), the necessary appliance sockets and the required wiring from the group switchboard or kitchen switch to the safety switch.
The Automation designer designs the UV-Turbo runtimes to match the kitchen runtimes.
UV-Turbo greasefilters are not allowed to run when the fan is off.
Motor operation is controlled by power supply via the automation system or via the switch at the kitchen.
A safety switch is compulsory and it should be situated close to the hood to a visible place in the kitchen. UV-Turbo’s are connected as own inputs to appliance for possible bran

The safety switch, appliance sockets and the cables marked with the dotted line are not included in the Jeven delivery.
Wiring diagram
Products which need to be wired are placed to to HPAC plan. Safety switch, switchgear and wiring from panelboard or kitchen switch to safety switch are placed to electrical plan.
Automation designer defines to the plans the running time of the UV-Turbo shall match to the running time of kitchen.

Electrician installs a mandatory safety switch to the appropriate location, installs and wires outlet box in the vicinity of the hood and wires junction boxes to UV-Turbos.